Water Cooled Refrigerated Air Dryers

Industrial water cooled refrigerated air dryers for reliable moisture removal and stable dew point control in large compressed air systems, using cooling water for efficient condenser heat rejection.

Custom-Engineered Water Cooled Refrigerated Air Dryer Systems up to 15,900 CFM

Lingyu provides industrial water cooled refrigerated air dryers for efficient moisture removal and stable pressure dew point control in medium and large compressed air systems. Our standard WH Series covers airflow capacities from 10.5 to 160 m³/min (approximately 371 to 5,650 CFM), using cooling water for efficient condenser heat rejection.

For large-flow industrial projects, custom-engineered water cooled refrigerated air dryer systems are available with capacities up to 15,900 CFM, configured according to actual airflow, operating pressure, inlet temperature, cooling-water conditions, required pressure dew point, power supply, and installation requirements.

Water cooled refrigerated air dryers are particularly suitable for facilities with centralized cooling-water systems, high ambient temperatures, limited compressor-room ventilation, or large continuous compressed air demand.

Water Cooled Refrigerated Air Dryers for Industrial Compressed Air Systems

Water cooled refrigerated air dryers remove moisture from compressed air using a refrigeration system with water as the condenser cooling medium.

Compared with air-cooled models, water-cooled dryers do not rely on compressor-room airflow for condenser heat rejection. They are particularly suitable for large compressed air systems, high ambient temperature installations, compressor rooms with limited ventilation, and facilities with centralized cooling-water systems.

Lingyu WH Series water cooled refrigerated air dryers provide airflow capacities from 10.5 to 160 m³/min (approximately 371 to 5,650 CFM) for medium and large industrial compressed air systems.

Water Cooled Refrigerated Air Dryer Capacity & Operating Conditions

ParameterSpecification
Airflow capacity10.5–160 m³/min
Approx. airflow371–5,650 CFM
Rated inlet pressure0.7 MPa
Operating pressure0.6–1.0 MPa
Rated inlet temperature50°C
Maximum inlet temperature≤80°C
Pressure dew point2–10°C
Pressure drop≤0.025 MPa
Rated ambient temperature32°C
Ambient operating range2–45°C
Cooling methodWater-cooled

For applications beyond the standard WH Series range, custom-engineered water cooled refrigerated air dryer systems are available for project capacities up to 15,900 CFM, as well as special working pressures, materials, and operating conditions.

How Does a Water Cooled Refrigerated Air Dryer Work?

Hot compressed air is first pre-cooled through a heat exchanger and then passes through the refrigeration evaporator, where its temperature is further reduced.

As the compressed air cools, water vapor condenses into liquid water. The condensate is separated and automatically drained before the dry air is reheated and returned to the downstream compressed air system.

Unlike an air-cooled dryer, heat from the refrigeration condenser is transferred to a cooling-water circuit rather than directly into the compressor room.

Cooling Water Requirements

A stable cooling-water supply is important for reliable water cooled refrigerated air dryer operation.

For the Lingyu WH Series:

Cooling Water ParameterRequirement
Cooling-water pressure0.2–0.4 MPa
Rated cooling-water temperature≤32°C
Operating water temperature2–38°C
Cooling-water flowModel dependent

Cooling-water flow increases with dryer capacity. The required flow should therefore be checked against the selected model before installation.

Facilities with an existing central cooling-water system or cooling tower are particularly suitable for water-cooled refrigerated dryers.

How to Select a Water Cooled Refrigerated Air Dryer

Select the dryer according to actual airflow and operating conditions rather than compressor capacity alone.

Selection ParameterCheck
Airflowm³/min or CFM
Working pressure0.6–1.0 MPa standard range
Inlet temperatureRated 50°C, max. ≤80°C
Required PDP2–10°C
Ambient temperature2–45°C
Cooling-water temperature≤32°C rated
Cooling-water pressure0.2–0.4 MPa
Cooling-water flowMatch selected model
Pressure drop≤0.025 MPa

For large compressed air systems, cooling-water capacity should be evaluated together with dryer airflow rather than selecting the dryer based only on compressor CFM.

When to Choose a Water Cooled Refrigerated Air Dryer

A water cooled refrigerated air dryer is particularly suitable when:

  • Large airflow capacity is required
  • Compressor-room ambient temperature is high
  • Ventilation or heat dissipation is limited
  • A centralized cooling-water system is already available
  • Large amounts of condenser heat should not be discharged into the compressor room
  • Stable cooling performance is required for continuous industrial operation

For installations without cooling water and with adequate ventilation, an air-cooled refrigerated air dryer is generally simpler to install.

Air Cooled vs Water Cooled Refrigerated Air Dryers

FactorAir CooledWater Cooled
Cooling mediumAmbient airCooling water
Cooling water requiredNoYes
Compressor-room ventilationMore importantLess dependent
Heat discharged into roomHigherLower
Large airflow systemsSuitableParticularly suitable
High ambient temperatureMore sensitiveMore suitable with proper cooling water
Central cooling-water facilityNot requiredIdeal
InstallationSimplerRequires water piping

Choose an air cooled refrigerated air dryer when cooling water is unavailable and adequate ventilation can be provided.

Choose a water cooled refrigerated air dryer when handling large airflow, operating in demanding compressor-room conditions, or when a centralized cooling-water system is already available.

Frequently Asked Questions

What is the capacity range of Lingyu water cooled refrigerated air dryers?

The WH Series covers 10.5 to 160 m³/min, approximately 371 to 5,650 CFM.

What cooling-water conditions are required?

The WH Series specifies cooling-water pressure of 0.2–0.4 MPa, rated cooling-water temperature of ≤32°C, and an operating water-temperature range of 2–38°C.

What is the pressure drop?

The specified pressure drop is ≤0.025 MPa under the applicable operating conditions.

Can a water cooled refrigerated dryer handle high inlet temperatures?

The WH Series has a rated inlet temperature of 50°C and a maximum inlet temperature of ≤80°C.

When should I choose water cooled instead of air cooled?

Water-cooled dryers are particularly suitable for large airflow systems, high ambient temperature installations, compressor rooms with limited ventilation, and facilities that already have centralized cooling water.

Regarding Water Cooled Refrigerated Air Dryers

Have questions? Contact us

FEEDBACK

Connect with us

Address

No. 22-1 to 22-3, Jinzhu Road, Heting Town, Heshan City, Jiangmen City, Guangdong Province

Phone

(WeChat/WhatsApp):+8615756650906

Phone

№1:(WeChat/WhatsApp):+8618628146428
№2:(WeChat/WhatsApp):+8613823294942

  • lingyudryer@gmail.com
  • Scan the code